CABLE SIZING CALCULATION:
Why do the calculation?
The
proper sizing of an electrical (load bearing) cable is important to ensure that
the cable can:
·
Operate
continuously under full load without being damaged
·
Withstand
the worst short circuits currents flowing through the cable
·
Provide
the load with a suitable voltage (and avoid excessive voltage drops)
·
(optional)
Ensure operation of protective devices during an earth fault
This
calculation can be done individually for each power cable that needs to be
sized, or alternatively, it can be used to produce cable sizing waterfall
charts for groups of cables with similar characteristics (e.g. cables installed
on ladder feeding induction motors).
All cable
sizing methods more or less follow the same basic six step process:
1) Gathering data about the
cable, its installation conditions, the load that it will carry, etc
2) Determine the minimum cable
size based on continuous current carrying capacity
3) Determine the minimum cable
size based on voltage drop considerations
4) Determine the minimum cable
size based on short circuit temperature rise
5) Determine the minimum cable
size based on earth fault loop impedance
6) Select the cable based on the
highest of the sizes calculated in step 2, 3, 4 and 5
The first
step is to collate the relevant information that is required to perform the
sizing calculation. Typically, you will need to obtain the following data:
The
characteristics of the load that the cable will supply, which includes:
·
Load
type: motor or feeder
·
Three
phase, single phase or DC
·
System /
source voltage
·
Full load
current (A) - or calculate this if the load is defined in terms of power (kW)
·
Full load
power factor (pu)
·
Locked
rotor or load starting current (A)
·
Starting
power factor (pu)
·
Distance
/ length of cable run from source to load - this length should be as close as
possible to the actual route of the cable and include enough contingency for
vertical drops / rises and termination of the cable tails
The basic
characteristics of the cable's physical construction, which includes:
·
Conductor
material - normally copper or aluminium
·
Conductor
shape - e.g. circular or shaped
·
Conductor
type - e.g. stranded or solid
·
Conductor
surface coating - e.g. plain (no coating), tinned, silver or nickel
·
Insulation
type - e.g. PVC, XLPE, EPR
·
Number of
cores - single core or multicore (e.g. 2C, 3C or 4C)
How the
cable will be installed, which includes:
·
Above
ground or underground
·
Installation
/ arrangement - e.g. for underground cables, is it directly buried or buried in
conduit? for above ground cables, is it installed on cable tray / ladder,
against a wall, in air, etc.
·
Ambient
or soil temperature of the installation site
·
Cable
bunching, i.e. the number of cables that are bunched together
·
Cable
spacing, i.e. whether cables are installed touching or spaced
·
Soil
thermal resistivity (for underground cables)
·
Depth of
laying (for underground cables)
·
For
single core three-phase cables, are the cables installed in trefoil or laid
flat?
Step 2: Cable Selection Based on Current Rating
Current
flowing through a cable generates heat through the resistive losses in the
conductors, dielectric losses through the insulation and resistive losses from
current flowing through any cable screens / shields and armouring.
The
component parts that make up the cable (e.g. conductors, insulation, bedding,
sheath, armour, etc) must be capable of withstanding the temperature rise and
heat emanating from the cable. The current carrying capacity of a cable is the
maximum current that can flow continuously through a cable without damaging the
cable's insulation and other components (e.g. bedding, sheath, etc). It is
sometimes also referred to as the continuous current rating or ampacity of a
cable.
Cables
with larger conductor cross-sectional areas (i.e. more copper or aluminium)
have lower resistive losses and are able to dissipate the heat better than
smaller cables. Therefore a 16 mm2 cable will have a higher
current carrying capacity than a 4 mm2 cable.
International
standards and manufacturers of cables will quote base current ratings of
different types of cables in tables such as the one shown on the right. Each of
these tables pertain to a specific type of cable construction (e.g. copper
conductor, PVC insulated, 0.6/1kV voltage grade, etc) and a base set of
installation conditions (e.g. ambient temperature, installation method, etc).
It is important to note that the current ratings are only valid for the quoted
types of cables and base installation conditions.
In the
absence of any guidance, the following reference based current ratings may be
used.
When the
proposed installation conditions differ from the base conditions, derating (or
correction) factors can be applied to the base current ratings to obtain the
actual installed current ratings.
International
standards and cable manufacturers will provide derating factors for a range of
installation conditions, for example ambient / soil temperature, grouping or
bunching of cables, soil thermal resistivity, etc. The installed current rating
is calculated by multiplying the base current rating with each of the derating
factors, i.e.
For
example, suppose a cable had an ambient temperature derating factor of kamb
= 0.94 and a grouping derating factor of kg = 0.85, then the
overall derating factor kd = 0.94x0.85 = 0.799. For a
cable with a base current rating of 42A, the installed current rating would be Ic
= 0.799x42 = 33.6A.
In the
absence of any guidance, the following reference derating factors may be used.
When
sizing cables for non-motor loads, the upstream protective device (fuse or
circuit breaker) is typically selected to also protect the cable against damage
from thermal overload. The protective device must therefore be selected to
exceed the full load current, but not exceed the cable's installed current
rating, i.e. this inequality must be met:
Motors
are normally protected by a separate thermal overload (TOL) relay and therefore
the upstream protective device (e.g. fuse or circuit breaker) is not required
to protect the cable against overloads. As a result, cables need only to be
sized to cater for the full load current of the motor, i.e.
Of
course, if there is no separate thermal overload protection on the motor, then
the protective device needs to be taken into account as per the case for
feeders above.
A cable's
conductor can be seen as an impedance and therefore whenever current flows
through a cable, there will be a voltage drop across it, which can be derived
by Ohm’s Law (i.e. V = IZ). The voltage drop will depend on two things:
·
Current
flow through the cable – the higher the current flow, the higher the voltage
drop
·
Impedance
of the conductor – the larger the impedance, the higher the voltage drop
The
impedance of the cable is a function of the cable size (cross-sectional area)
and the length of the cable. Most cable manufacturers will quote a cable’s
resistance and reactance in Ω/km. The following typical cable impedances for
low voltage AC and DC single core and multicore cables can be used in the
absence of any other data.
For AC
systems, the method of calculating voltage drops based on load power factor is
commonly used. Full load currents are normally used, but if the load has high
startup currents (e.g. motors), then voltage drops based on starting current
(and power factor if applicable) should also be calculated.
Maximum Permissible Voltage Drop
It is
customary for standards (or clients) to specify maximum permissible voltage
drops, which is the highest voltage drop that is allowed across a cable. Should
your cable exceed this voltage drop, then a larger cable size should be
selected.
Maximum
voltage drops across a cable are specified because load consumers (e.g.
appliances) will have an input voltage tolerance range. This means that if the
voltage at the appliance is lower than its rated minimum voltage, then the
appliance may not operate correctly.
In
general, most electrical equipment will operate normally at a voltage as low as
80% nominal voltage. For example, if the nominal voltage is 230VAC, then most
appliances will run at >184VAC. Cables are typically sized for a more
conservative maximum voltage drop, in the range of 5 – 10% at full load.
It may be
more convenient to calculate the maximum length of a cable for a particular
conductor size given a maximum permissible voltage drop (e.g. 5% of nominal
voltage at full load) rather than the voltage drop itself. For example, by
doing this it is possible to construct tables showing the maximum lengths
corresponding to different cable sizes in order to speed up the selection of
similar type cables.
The
maximum cable length that will achieve this can be calculated by re-arranging
the voltage drop equations and substituting the maximum permissible voltage
drop (e.g. 5% of 415V nominal voltage = 20.75V). For a three phase system:
During a
short circuit, a high amount of current can flow through a cable for a short
time. This surge in current flow causes a temperature rise within the cable.
High temperatures can trigger unwanted reactions in the cable insulation,
sheath materials and other components, which can prematurely degrade the
condition of the cable. As the cross-sectional area of the cable increases, it
can dissipate higher fault currents for a given temperature rise. Therefore,
cables should be sized to withstand the largest short circuit that it is
expected to see.
The
minimum cable size due to short circuit temperature rise is typically
calculated with an equation of the form:
The
temperature rise constant is calculated based on the material properties of the
conductor and the initial and final conductor temperatures (see the derivation
here). Different international standards have different treatments of the
temperature rise constant, but by way of example, IEC 60364-5-54 calculates it
as follows:
The
initial conductor temperature is typically chosen to be the maximum operating
temperature of the cable. The final conductor temperature is typically chosen
to be the limiting temperature of the insulation. In general, the cable's
insulation will determine the maximum operating temperature and limiting
temperatures.
As a
rough guide, the following temperatures are common for the different insulation
materials:
Material
|
Max Operating Temperature oC
|
Limiting Temperature oC
|
PVC
|
75
|
160
|
EPR
|
90
|
250
|
XLPE
|
90
|
250
|
The short
circuit energy is normally
chosen as the maximum short circuit that the cable could potentially
experience. However for circuits with current limiting devices (such as HRC
fuses), then the short circuit energy chosen should be the maximum prospective
let-through energy of the protective device, which can be found from
manufacturer data.
Sometimes
it is desirable (or necessary) to consider the earth fault loop impedance of a
circuit in the sizing of a cable. Suppose a bolted earth fault occurs between
an active conductor and earth. During such an earth fault, it is desirable that
the upstream protective device acts to interrupt the fault within a maximum
disconnection time so as to protect against any inadvertent contact to exposed
live parts.
Ideally
the circuit will have earth fault protection, in which case the protection will
be fast acting and well within the maximum disconnection time. The maximum
disconnection time is chosen so that a dangerous touch voltage does not persist
for long enough to cause injury or death. For most circuits, a maximum
disconnection time of 5s is sufficient, though for portable equipment and
socket outlets, a faster disconnection time is desirable (i.e. <1s and will
definitely require earth fault protection).
However
for circuits that do not have earth fault protection, the upstream protective
device (i.e. fuse or circuit breaker) must trip within the maximum
disconnection time. In order for the protective device to trip, the fault
current due to a bolted short circuit must exceed the value that will cause the
protective device to act within the maximum disconnection time. For example,
suppose a circuit is protected by a fuse and the maximum disconnection time is
5s, then the fault current must exceed the fuse melting current at 5s (which
can be found by cross-referencing the fuse time-current curves).
By simple
application of Ohm's law:
It can be
seen from the equation above that the impedance of the earth fault loop must be
sufficiently low to ensure that the earth fault current can trip the upstream
protection.
The earth
fault loop can consist of various return paths other than the earth conductor,
including the cable armour and the static earthing connection of the facility.
However for practical reasons, the earth fault loop in this calculation
consists only of the active conductor and the earth conductor.
The earth
fault loop impedance can be found by:
In this
example, we will size a cable for a 415V, 30kW three-phase motor from the MCC
to the field.
The
following data was collected for the cable to be sized:
·
Cable
type: Cu/PVC/GSWB/PVC, 3C+E, 0.6/1kV
·
Operating
temperature: 75C
·
Cable
installation: above ground on cable ladder bunched together with 3 other cables
on a single layer and at 30C ambient temperature
·
Cable
run: 90m (including tails)
·
Motor
load: 30kW, 415V three phase, full load current = 61A, power factor = 0.85
·
Protection:
aM fuse of rating = 80A, max prospective fault I2t =
90 A2s , 5s melt time = 550A
Suppose
the ambient temperature derating is 0.89 and the grouping derating for 3
bunched cables on a single layer is 0.82. The overall derating factor is 0.89 0.82 = 0.7298. Given
that a 16 mm2 and 25 mm2 have base current ratings of 80A and
101A respectively (based on Reference Method E), which cable should be selected
based on current rating considerations?
The
installed current ratings for 16 mm2 and 25 mm2
is 0.7298 80A = 58.38A and
0.7298 101A = 73.71A
respectively. Given that the full load current of the motor is 61A, then the
installed current rating of the 16 mm2 cable is lower than
the full load current and is not suitable for continuous use with the motor.
The 25 mm2 cable on the other hand has an installed current
rating that exceeds the motor full load current, and is therefore the cable
that should be selected.
Suppose a
25 mm2 cable is selected. If the maximum permissible voltage
drop is 5%, is the cable suitable for a run length of 90m?
A 25 mm2
cable has an ac resistance of 0.884 Ω/km and an ac reactance of 0.0895 Ω/km.
The voltage drop across the cable is:
A voltage
drop of 7.593V is equivalent to ,
which is lower than the maximum permissible voltage dorp of 5%. Therefore the
cable is suitable for the motor based on voltage drop considerations.
The cable
is operating normally at 75C and has a prospective fault capacity (I2t)
of 90,000 A2s. What is the minimum size of the cable
based on short circuit temperature rise?
PVC has a
limiting temperature of 160C. Using the IEC formula, the short circuit
temperature rise constant is 111.329. The minimum cable size due to short
circuit temperature rise is therefore:
In this example,
we also use the fuse for earth fault protection and it needs to trip within 5s,
which is at the upper end of the adiabatic period where the short circuit
temperature rise equation is still valid. Therefore, it's a good idea to also
check that the cable can withstand the short circuit temperature rise for for a
5s fault. The 80A motor fuse has a 5s melting current of 550A. The short
circuit temperature rise is thus:
Therefore,
our 25 mm2 cable is still suitable for this application.
Suppose
there is no special earth fault protection for the motor and a bolted single
phase to earth fault occurs at the motor terminals. Suppose that the earth
conductor for our 25 mm2 cable is 10 mm2.
If the maximum disconnection time is 5s, is our 90m long cable suitable based
on earth fault loop impedance?
The 80A
motor fuse has a 5s melting current of 550A. The ac resistances of the active
and earth conductors are 0.884 Ω/km and 2.33 Ω/km) respectively. The reactances
of the active and earth conductors are 0.0895 Ω/km and 0.0967 Ω/km)
respectively.
The
maximum length of the cable allowed is calculated as:
The cable
run is 90m and the maximum length allowed is 108m, therefore our cable is
suitable based on earth fault loop impedance. In fact, our 25 mm2
cable has passed all the tests and is the size that should be selected.
Comments
Post a Comment